Air-Cooled Portable Water Chiller - 2.9 Ton Capacity (CG-3A)


Descripción

Specifications
Model: CG-3A (1)
Capacity
  • (2) Tons : 2.9
  • kW : 10.8

Compressor

  • HP : 3
  • Type : Hermetic

Process Pump

  • HP : 3/4
  • GPM : 7.2
  • PSI : 30
  • Type : Centrifugal
  • Construction : Stainless Steel
  • Automatic Low Flow Bypass: : Standard

Air-Cooled Condenser

  • Type : Fan
  • CFM : 3,000
  • (3) Ambient : 95°F

Refrigerant

  • Type : R-410A

Full Load Amperage (4)

  • 230/1/60: 20
  • 460/3/60: 10

Reservoir Capacity

  • Holding : 7.5 gal
  • Lid : Optional
  • Auto Make-Up : Optional

Process Connections

  • To Process : 1"
  • From Process : 1"

Dimensions

  • Height : 43"
  • Width : 34"
  • Depth : 40"

Weight (5)

  • Shipping : 600 lbs

Specification Notes:

1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.

2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ " 115°F condensing temperature. Capacities may be +/- 5% as reserved by the compressor manufacturer. Operating at temperatures below 50° will reduce chiller capacity. The minimum recommended operating temperature when no glycol is used is 48°F.

3. Design ambient conditions. Loss of capacity and/or difficulty operating will occur at higher ambients. Minimum recommended ambient is 60°F.

4. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring.

5.Approximate unit weight crated for shipment.

También le puede interesar

Recién vistos